CB-2000

“Take the CB-PRO and make it better!”  That is what AMR’s engineers were told to do, and they did it.  A new processor core has been added with expanded memory and faster processing/sampling speed.  Previously, unique firmware was installed on each unit based upon customer preferences (e.g. communications, enable/disable certain features, etc.). Now, all features are available and user selectable, and there’s room for expansion. If a customer has a set of specific settings for cable(s) or machine(s), we can set up an option where the user selects the cable or machine and all settings are preset.  User interface is easier to navigate and scroll through.  A backlit display is used to make the screens easier to see in low light conditions.  Some customers had nuisance tripping on Phase Current Imbalance. This has been eliminated.  The CB-2000’s enclosure is physically stronger and more environmentally sealed.  It is a direct drop-in replacement for the CB-PRO, same exact footprint and wiring. For a detailed description and printable information, click below to view the CB-2000 cut sheet.

ENCLOSURE DIMENSIONS 5.5″W x 6.625″H x 4.625″D (139.7mm x 168.28mm x 117.48mm)
ENCLOSURE RATING Panel Mount, Powder Coated Aluminum
UNIT WEIGHT 3 LBS (1.36 KG)
CONTROL VOLTAGE 90-130 VAC
OPERATING VOLTAGE 480-1000 VAC
BACKUP BATTERY NO
INTERRUPTING CURRENT 100,000 Amps
OPERATING CURRENT 10-550 Amps
OPERATING TEMPERATURE -40 TO 135 F
THERMAL TRIP TIME ACCURACY +/- 10%
INSTANTANEOUS (MAG) TRIP RANGE 2x to 16x (x=Continuous Current)
MAGNETIC TRIP ACCURACY +/- 10%
GROUND FAULT PROTECTION Adjustable from 1-25 Amps in 0.1 A Increments
GROUND FAULT TRIP ACCURACY +/- 20% @ 1-2 Amps and +/- 10% @ 2.1-25 Amps
LOW CONTROL VOLTAGE Three phase circuit opens when control voltage is 80-85 VAC
LOW THREE PHASE VOLTAGE Adjustable from 1-50%
PHASE CURRENT IMBALANCE Adjustable from 1-50 %
LOW PHASE VOLTAGE DELAY Adjustable from 1-5 seconds
PHASE CURRENT IMBALANCE DELAY Adjustable from 1-5 seconds
DISPLAY 4 line x 20 character LCD with LED Indicators
COMMUNICATION PROTOCOLS RS-485 @ 38.4 kBd, Modbus, or Stand Alone
ADDRESS RANGE 0-255
CLOSE SWITCH 2 second hold with adjustable 0-10 second contractor close delay
WARRANTY 1 Year

Head Office

PO Box 234
12187 N Scenic Highway
Rocky Gap, VA 24366

T:  +1-800-541-5583
P:
  +1-276-928-1712
F:  +1-276-928-1815

Hours of operation:
Monday - Friday
8:00AM - 4:30PM EST

Bluefield Facility

1960 Valley Dale Street
Bluefield, VA 24605-9454

GPS > 700 Fincastle Tnpk

T:  +1-800-428-7800
P:  +1-276-326-2611

Hours of operation:
Monday - Friday
8:00AM - 5:00PM EST

Contact Us