Solutions

CB-2000

Features & Benefits

“Take the CB-PRO and make it better!”  That is what AMR’s engineers were told to do, and they did it.  A new processor core has been added with expanded memory and faster processing/sampling speed.  Previously, unique firmware was installed on each unit based upon customer preferences (e.g. communications, enable/disable certain features, etc.). Now, all features are available and user selectable, and there’s room for expansion. If a customer has a set of specific settings for cable(s) or machine(s), we can set up an option where the user selects the cable or machine and all settings are preset.  User interface is easier to navigate and scroll through.  A backlit display is used to make the screens easier to see in low light conditions.  Some customers had nuisance tripping on Phase Current Imbalance. This has been eliminated.  The CB-2000’s enclosure is physically stronger and more environmentally sealed.  It is a direct drop-in replacement for the CB-PRO, same exact footprint and wiring. For a detailed description and printable information, click below to view the CB-2000 cut sheet.

Resources

Specifications

ENCLOSURE DIMENSIONS:
5.5″W x 6.625″H x 4.625″D (139.7mm x 168.28mm x 117.48mm)

ENCLOSURE RATING:
Panel Mount, Powder Coated Aluminum

UNIT WEIGHT:
3 LBS (1.36 KG)

CONTROL VOLTAGE:
90-130 VAC

OPERATING VOLTAGE:
480-1000 VAC

BACKUP BATTERY:
NO

INTERRUPTING CURRENT
100,000 Amps

OPERATING CURRENT
10-550 Amps

OPERATING TEMPERATURE:
-40 TO 135 F

THERMAL TRIP TIME ACCURACY
+/- 10%

INSTANTANEOUS (MAG) TRIP RANGE
2x to 16x (x=Continuous Current)

MAGNETIC TRIP ACCURACY
+/- 10%

GROUND FAULT PROTECTION
Adjustable from 1-25 Amps in 0.1 A Increments

GROUND FAULT TRIP ACCURACY
+/- 20% @ 1-2 Amps and +/- 10% @ 2.1-25 Amps

LOW CONTROL VOLTAGE
Three phase circuit opens when control voltage is 80-85 VAC

LOW THREE PHASE VOLTAGE
Adjustable from 1-50%

PHASE CURRENT IMBALANCE
Adjustable from 1-50 %

LOW PHASE VOLTAGE DELAY
Adjustable from 1-5 seconds

PHASE CURRENT IMBALANCE DELAY
Adjustable from 1-5 seconds

DISPLAY
4 line x 20 character LCD with LED Indicators

COMMUNICATION PROTOCOLS
RS-485 @ 38.4 kBd, Modbus, or Stand Alone

ADDRESS RANGE
0-255

CLOSE SWITCH
2 second hold with adjustable 0-10 second contractor close delay

WARRANTY
1 Year