Solutions

GM-300

AMR PEMCO’s GM-300 Ground Check system is intended for use on all high voltage systems where a pilot wire is available. Ground Check systems using the GM-300 are suitable for applications on power systems up to 25kVAC including low and medium voltages. For power systems over 25kV, contact us for recommendations.

Features & Benefits

  • Test Switch included
  • Versatile sensitivity adjustment
  • Long life LED indicator lights
  • Low and high resistance indications
  • Simple troubleshooting
  • Reduced nuisance trips
  • Field replacement boards
  • Plug-in relay
  • Optional mechanical trip indicator
  • Operating window width of 3 ohms
  • MSHA approval #041890AMR

Resources

Specifications

  • Dimensions: 7″W x 9.5″H x 6″D (177.8mm x 241.3 x 152.4)
  • Enclosure Rating: NEMA 4X, Powder Coated Aluminum
  • Weight: 6 lbs (2.7kg)
  • Installation: Front Instrument Panel Mount
  • Operating Voltage: 120 VAC
  • Current Consumption: 750 mA
  • Operating Temperature: -20 to 70C
  • Humidity: 0 to 90% R.H.
  • Phase Voltage Filters: 7.2 kV, 15 kV, or 25 kV
  • Sensitivity: 3 ohms
  • Trip Resistance: +/-1.5 ohms
  • Trip Delay: No
  • Pilot Voltage: 12 VDC
  • Outputs: (1) Normally open or Normally Closed Contact Relay-250VAC @ 10 A
  • Display: LED indicators
  • Backup Battery: OPTIONAL – Rechargeable 12VDC, 12 Ahr
  • Test Feature: Yes
  • Option: Blocking Inductor-prevents parallel earth pass of signal
  • Warranty: 90 Days